ZDMS0.8/20S-PSZS8/20

  • Detail

Product details 

Automatic fire gun fire extinguishing installation is composed of fire gun body, signal processor and field manual control panel. It combines micro-control technology, infrared / ultraviolet sensing detection technology, mechanical rotation control technology, image transmission technology, automatically find the accurate location of the ignition point and effectively and quickly extinguish the fire source. According to the ignition point, DC or spray can be used to put out the fire effectively, but also to protect the safety of person and property, and has the function of manual operation control and image display on the spot. The fire source can be detected by forced start according to the linkage signal of other fire alarm systems, and the ability of anti-environmental interference can be improved by using infrared / ultraviolet dual-band detection technology to detect the fire source effectively and at the same time to improve the ability to resist environmental interference. The ground sensitivity parameters can be set and debugged.  

Product parameters     

Model 
Performance parameter

 

ZDMS0.8/20S 
PSZS8/20


ZDMS0.8/30S 
PSZS9/30

 

ZDMS0.80/40S-TY

 

ZDMS0.8/30P-TY泡沫

Fixed working pressure

0.8MPa

0.8MPa

0.8MPa

0.8MPa

Working pressure upper limit

1.6MPa

1.6MPa

1.6MPa

1.6MPa

Rated flow

20L/S

30L/S

40L/S

30L/S

Protection radius

50m

55m

60m

45m

俯仰回转角 
Overlooking return angle

-90°~60°(adjustable) 

-90°~60°(adjustable)

-90°~60°(adjustable)

-90°~60°(adjustable)

Targeting time

60s

60s

60s

60s

Power line voltage

24VDC

24VDC

24VDC

24VDC

Biggest actuation power

130W

130W

130W

130W

Installation height

8〜30

8〜30

8〜30

8〜30

Monitoring radius

80m

80m

80m

80m

                                Jet medium

water

water

water

foam/water

Performance feature

=Large flow, long range, and faster to extinguish early fires
=The rotating mechanism has clutch function to protect the motor effectively 
=With electrically operated column/fog nozzles
=Dual-band detection can effectively improve anti-jamming capability
=It has field manual control function
=It has the function of image transmission
=With other fire alarm system linkage function
=Field ground sensitivity parameter setting, convenient for debugging

{"serList":[{"icon":"iconfront front-shouye","status":"1","isSys":"1","title":"Home","url":"index.html","type":"index"},{"icon":"iconfront front-weibiaoti-","status":"1","isSys":"1","title":"Tel","phone":"075781284002","type":"tel","color":""},{"icon":"iconfront front-pinglun","status":"1","isSys":"1","title":"Guestbook","url":"msg.html","type":"msg"},{"icon":"iconfront front-didianmianxing","status":"1","isSys":"1","title":"Map","url":"map.html","type":"map"},{"icon":"iconfront front-duanxin","status":"0","isSys":"1","title":"短信","phone":"13800138000","type":"sms"},{"icon":"layui-icon layui-icon-share","status":"0","isSys":"1","title":"分享","shareList":["weixin","weibo","qq","qqZone","douban","tieba","copy"],"type":"share"}],"hasEdit":true}